NHA86312-00 Fan Power Control Board
The Schneider NHA86312-00 is the fan power and control board used in high-power Altivar ATV610, ATV630, and ATV930 drives, covering the 220–315 kW range (commonly associated with size 6 / 315 kW frames). It carries the spare-part designation VX4VP1400. Its function is to regulate and supply power to the heatsink cooling fans, translating the drive’s thermal management commands into fan speed and on/off control. In ATV610/630/930 drives, the fan mode can be configured as Standard (fan active whenever the motor is running), Always (fan permanently active), or Economy (fan activates based on the drive’s internal thermal state). The fan control board is the hardware that executes this logic.
This is a power-management module for the cooling system, not the fan assembly itself and not the main control board. Supplied as a tested replacement unit, it is intended for cases where the fan control board is confirmed faulty, or where fan operation is abnormal despite a serviceable fan and clean airflow path.
| Specification | Details |
|---|---|
| Part Number | NHA86312-00 |
| Spare-Part Designation | VX4VP1400 |
| Product Type | Fan Power / Control Board |
| Compatible Drives | ATV610 / ATV630 / ATV930 (high-power models) |
| Power Range | 220 kW – 315 kW (frame-dependent; commonly size 6) |
| Function | Heatsink fan power supply and speed / on-off control |
| Associated Drive Fault | OHF — Drive overheat (thermal state ≥ 118%) |
| Fan Modes (Drive-Side) | Standard / Always / Economy (configurable in drive menu) |
| Condition | Tested replacement unit |
Important Diagnostic Boundary: The NHA86312-00 is not the fan itself. It is the electronic board that powers and controls the fan. If the drive trips on OHF, the correct diagnostic sequence is to first confirm whether the fan is physically running, whether the impeller is blocked or contaminated, and whether the airflow path is clear — before concluding the fan control board is defective. A dead fan and a faulty control board produce the same OHF symptom from the drive’s perspective.

The fan control board becomes the primary suspect under these conditions:
Critical caution: Before replacing the board, confirm the fan motor itself is serviceable (free rotation, no bearing noise, no physical obstruction) and that the heatsink fins and airflow path are not clogged. A blocked or worn fan will cause OHF even with a perfectly functional NHA86312-00.
Before ordering, confirm the following:

No. It is the fan power and control board only. The heatsink fan assembly is a separate component. Confirm whether the fan motor or the control board is faulty before ordering.
No. OHF is triggered when the drive’s thermal state reaches 118%. A blocked fan impeller, a worn fan motor, clogged heatsink fins, or high ambient temperature can all produce OHF with a perfectly functional NHA86312-00. Check the fan’s physical operation and airflow path first.
Yes, on supported firmware versions the fan mode can be set to Standard, Always, or Economy in the drive’s maintenance menu. If the fan does not respond to these settings, the control board or fan wiring should be investigated
Contact sales
E-mail: 1225353621a@gmail.com
Mobile:+86 15903995069
Whatsapp:+86 15903995069
WeChat:+8615903995069
Our products
We are an international supplier of industrial automation spare parts, providing tens of thousands of industrial automation products for users.
Even if the product you are looking for is not on our website, we may have the spare parts you are looking for.
Please contact us and we will serve you as soon as possible.